APC-2
Created: 2025-12-22
•
Updated: 2025-12-22
Relationships
Loading...
Attachments
Loading...
Comments (2)
agent
·
2025-12-22
[QA] ✅ VERIFICATION PASSED
**Comprehensive QA completed with the following results:**
✅ All 22 unit tests pass (100% success rate)
✅ All requirements from issue verified and met
✅ SNMP client wrapper implemented correctly with pysnmp>=7.0.0
✅ OID constants properly defined for rPDU2 subtree (.1.3.6.1.4.1.318.1.1.26)
✅ Connection handling with 5s timeout and 3 retries verified
✅ Code quality: High (type hints, docstrings, logging, error handling)
✅ Security: No vulnerabilities detected (no hardcoded credentials, proper settings usage)
✅ Edge cases tested and validated (outlet number boundaries, unit conversion)
✅ Async implementation verified for all methods
✅ Resource cleanup (close) works correctly
**Files verified:**
- app/services/snmp_client.py (504 lines)
- app/services/__init__.py (5 lines)
- tests/test_snmp_client.py (337 lines)
- pyproject.toml (dependency added)
**Note:** Live PDU testing could not be verified from QA environment (network limitation), but implementation agent reported successful testing against 192.168.1.65.
**Recommendation:** APPROVED FOR PRODUCTION
Detailed QA report: /tmp/qa-APC-2.md
agent
·
2025-12-22
Implemented SNMP client service for APC PDU communication.
**Changes made:**
- Added pysnmp>=7.0.0 dependency to pyproject.toml
- Created app/services/snmp_client.py with:
- OID constants for rPDU2 subtree (device info, phase status, outlet config/status/control/metering)
- OutletState and OutletCommand enums matching APC spec values
- SNMPClient class with connection handling, 5s timeout, 3 retries (configurable)
- Methods: get(), get_many(), set(), walk()
- Convenience methods: get_outlet_state(), get_outlet_name(), get_outlet_current(), set_outlet_command()
- get_device_info() and get_phase_status() for device monitoring
- Custom exceptions: SNMPError, SNMPTimeoutError, SNMPConnectionError
- Created tests/test_snmp_client.py with 22 unit tests
**Verification:**
- All 22 unit tests pass
- Live testing against PDU at 192.168.1.65:
- Successfully read device info (AP8641, firmware 6.5.6)
- Successfully read phase status (244V, 1.4A, 33W)
- Successfully read outlet states/names (24 outlets)
- Successfully read outlet current values
- WALK operation works correctly